ZEBRONICS Online UPS is specifically designed for operations in power areas. They provide high power density with long backup time in compact size. It’s ideal for ATMs, banking and other businesses with critical applications. Users could also adjust charging current from 1A to 6A according to different applications. Comprehensive display allows easy monitoring and access of UPS status with (EPO) Emergency power off function.
Features
True double-conversion | |
Microprocessor control optimizes reliability | |
Wide input voltage (110 V —300 V) | |
Converter mode available | |
ECO mode for energy saving (Only available for 1-3KVA) | |
Generator compatible | |
Smart SNMP works well with either USB or RS-232 together | |
Comprehensive display allows easy monitoring and access of UPS status | |
Input power factor correction | |
Adjustable battery number | |
Emergency power off (EPO) function | |
Country of Origin : China |
Specifications
MODEL | ZEB-OU10KE16 | |
Phase | 1-phase in / 1-phase out | |
Capacity | 10000 VA 8000W | |
INPUT | ||
Nominal Voltage | 208/220/230/240VAC | |
Voltage Range | 110-300 VAC (Based on load at 50%) 176-300 VAC (Based on load at 100%) | |
Frequency Range | 46~54 Hz or 56~64 Hz | |
Power Factor | ≥0.99 @ 100% Load | |
OUTPUT | ||
Output Voltage | 208/220/230/240VAC | |
AC Voltage Regulation (Batt. Mode) | ± 1% | |
Frequency Range (Synchronized Range) | 46~54Hz | |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz | |
Current Crest Ratio | 3:1 (max.) | |
Harmonic Distortion | ≦ 3 % THD (Linear Load) | |
≦ 5 % THD (Non-linear Load | ||
Transfer Time | AC Mode to Batt. Mode : Zero | |
Inverter to Bypass : Zero | ||
Waveform (Batt. Mode) | Pure Sine wave | |
EFFICIENCY | ||
AC Mode | 93.00% | |
BATT Mode | 91.00% | |
BATTERY | ||
Numbers | 16 ~ 20 (Adjustable)* | |
Typical Recharge Time | 9hrs recover to 90% capacity | |
Battery Type | SMF/VRLA | |
Charging Current (max.) | 1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries | |
Charging Voltage | 13.65 x N (N-Number of battery | |
INDICATORS | ||
LCD Display | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions | |
ALARM | ||
Battery Mode | Sounding every 4 seconds | |
Low Battery | Sounding every second | |
Overload | Sounding twice every second | |
Fault | Continuously sounding | |
PHYSICAL | ||
Dimension,DxWxH (mm) | 442 x 190 x 318 | |
Net Weight (kgs) | 16 | |
ENVIRONMENT | ||
Operation Humidity | 0-95% RH @ 0-40°C (non-condensing | |
Noise Leve | Less than 58dB @ 1 Meter | |
MANAGEMENT | ||
Smart RS-232 / USB | Supports Windows 2 2000/2003/XP/Vista/2008, Windows2 7/8/10, Linux and MAC | |
Optional SNMP | Power management from SNMP manager and web browser |